Return to Interactive Feature Homepage
Download
a "printer-friendly" PDF version
Steam
Valves: Commissioning Tips
Overcoming
common field problems related to steam-piping systems
By DAVID
A. SELLERS, PE
Portland Energy Conservation Inc.
Portland, Ore.
Over the past
20 to 30 years, as improved building envelopes and other technological
advances have eliminated the need for steam radiators as a method
of handling perimeter heating loads, steam-piping systems have become
less and less common in buildings, replaced with forced hot water
and other approaches.
With the decline
in steam heating has come a decline in the number of practitioners
familiar with the science behind it, especially ones with hands-on
experience in the design and application of this type of system.
This can become a serious issue when an existing steam-piping network
must be modified or extended to serve new loads. Even though many
of the materials and methods associated with steam systems are similar
to those associated with hot-water systems, there are fundamental
differences between the two that make some techniques and approaches
used for one totally inappropriate for use with the other. If these
differences are not addressed by the designer or installer, they
will become commissioning and operational problems that can plague
a system throughout its life.
This article
discusses some of the more common commissioning and operational
problems encountered with steam-piping systems, including the theories
behind them and techniques that can be used to overcome them.
Valve-Sizing
Problems
From an operational
standpoint, few things are more frustrating than an oversized steam
valve and the pressure and temperature swings it can cause. Often,
this instability cascades into other portions of the system, compounding
the headaches and energy waste (Figure 1).
FIGURE 1. A low-flow condition associated with a new unoccupied
mode creates a pseudo-oversized condition with the preheat-coil
control valve and mixed-air dampers, resulting in instability that
"disappears" when the occupied cycle resumes.
Sizing a steam
valve involves determining the proper flow coefficient (Cv)
for the application. This involves selecting a valve so that at
design flow, it has a pressure drop that is significant relative
to the system it is serving.1
The flow through
a steam valve can become supersonic under some conditions. When
this happens, the downstream pressure no longer has any impact on
the flow through the valve, and the valve's capacity becomes a function
of the entering pressure. One can determine the potential for critical
or non-critical flow based on the difference between the absolute2
entering and leaving pressures anticipated at the valve. If the
absolute leaving pressure is greater than 58 percent of the absolute
entering pressure, the flow through the valve is deemed non-critical,
and the valveÍs flow capacity becomes a function of both the entering
and leaving pressures. Under these conditions, the following equation
would be used to size the valve:3
Equation
(1)
where: Cv
= Flow coefficient
ws
= Steam flow in pounds per hour
K = 1 + (0.0007
X superheat in F)
P1
= Absolute entering steam pressure in psia
P2
= Absolute leaving steam pressure in psia
For critical
flow (the absolute leaving pressure is less than 58 percent of the
absolute entering pressure), the sizing equation is much simpler:
Equation
(2)
Another important
consideration in selecting steam valves is flow characteristic.
Ideally, a valve's flow characteristic complements the flow-related
performance curves of the load served and provides a linear relationship
between valve stroke and load performance.4
Even when a
steam valve is properly sized for the design load, the large system
turndown ratios associated with some steam loads can cause oversizing-like
problems under low-load conditions. Approaches that employ two control
valves piped in parallel often are used to address this problem
(Figure 2). The load split between the two valves usually is between
50/50 and 30/70. A variety of control strategies are used with this
configuration, including:
FIGURE 2. A typical multiple-steam-valve arrangement serving
a steam heat exchanger (STHX). Note the different valve sizes, as
can be seen from the different flow-coefficient and flow ratings.
- Modulating
both valves with the same signal. Although this approach is
simple and usually an improvement over having one large valve,
it does not take full advantage of the potential for improved
control.
- Sequencing
the valves so that one must be fully open before the other starts
to open. This usually is an improvement over the first approach,
but still can show some instability as the load transitions between
valves, especially if the second valve is large relative to the
first valve.
- Using
the smaller valve at low-load conditions, then switching valves.
This approach uses the smaller valve until it no longer can meet
the load, then switches to the larger valve, which is used until
it is at maximum capacity. The smaller valve then is used in sequence
with the larger valve to handle peak-load conditions. This approach
works well and is easier to implement with direct-digital-control
(DDC) systems than it is with discrete control components.
- Adjusting
the larger valve as required to keep the smaller valve at mid-stroke.
This is an unusual but innovative approach that has its roots
in the process-control industry. It commonly is called "course/fine
control." It uses the smaller valve to maintain the set point
and the larger valve to take up the offset that occurs when the
smaller valve no longer can maintain the set point. One way to
achieve this involves the use of a proportional-integral-derivative
(PID) loop for the smaller valve and an integral-only loop for
the larger valve.5 This approach also lends itself
to DDC systems.
For smaller
loads, self-contained valves provide individualized control of steam
radiators and convectors at less cost than electrically or pneumatically
actuated valves. And because the valves are intended to serve small
heat exchangers, the Cv selection often is better.
Heat
Problems
A steam system
operates at high temperatures. This, in turn, elevates the temperatures
of:
- Metals
in direct contact with the piping (conductive heat transfer).
- Objects
in a line-of-sight path with the uninsulated portion of the system
(radiant heat transfer).
- Objects
located above the pipe (convective heat transfer).
These elevated
temperatures can have an adverse effect on some of the flexible
materials used in pneumatic valves and the electronics and electrical
equipment used in electrically actuated valves. To minimize the
potential for damage and/or premature failure, consider:
- Providing
radiation shields between the valve actuator and valve body.
Usually, this simply is a piece of reflective metal installed
between the actuator and valve.
- Installing
the valve so that the actuator is at an angle to the pipe instead
of directly above it. This removes the valve from the primary
convective path.6
- Making
an effort to have the control-valve bodies and the piping in the
immediate vicinity of the actuators insulated prior to start-up,
if the system is going to be placed on line prior to completion
of the insulation process.
- Insulating
control valves with removable insulation jackets (Photo A).
This will allow mechanics to open and service the valves without
damaging the insulation.
PHOTO A. A removable valve-insulation jacket.
Start-up
Problems
Closing the
service valves to portions of a large steam-distribution system
during periods of inactivity eliminates parasitic energy losses
that can rival the thermal requirements of the loads actually being
served. Reopening these valves, however, is no casual undertaking.
The reasons are varied:
- Thermal
expansion places significant loads on the anchor and guide systems
and their associated expansion-control systems.
- Warm-up
requirements can place significant loads on drip traps. These
loads can be far greater than those seen in normal service.7
- Condensate
trapped in a cold piping system by failed traps or improperly
pitched and drained piping and/or a large warm-up condensate burden
can cause flow- and condensation-induced waterhammer.8
For these reasons,
the start-up of a steam-piping system should be a carefully planned
event, one coordinated and performed by experienced engineers and
operators. Automating the start-up of anything but a relatively
small, low-pressure network is a task probably best not undertaken.
If you find yourself commissioning a project involving an automated
start-up of portions of a steam-distribution system, consider:
- Performing
an automated start-up only on a low-pressure steam header and
only if the facility has a good maintenance program, one that
will ensure that all drip traps are fully functional.
- Making
sure that the piping system is well-designed and arranged to ensure
good drainage and to handle the condensate loads associated with
warming it.
- Providing
equipment and programming that will allow the automation system
to perform the same procedure that would be used by operators
to bring the piping system on line. Typical considerations include:
a) Providing
a modulating signal to the control valve, even though the valve
is line size and providing an on/off control function. This
allows the system to crack open the valve and hold it at that
position to warm the main and then gradually ramp open the valve.
b) Ensuring
that there are no software problems or operating triggers that
will rapidly cycle the valve.
c) Taking
steps to physically limit the speed at which the valve can open.
With electrically driven valves, this can be done by using a
slow actuator. With pneumatically actuated valves, it can be
done by restricting the pneumatic air supply. Photo B shows
a typical micrometer-style needle valve that can be employed
for this purpose.
PHOTO
B. A micrometer-style needle valve that can be used to control the
rate of movement of a pneumatic valve.
d) Installing
interlocks to prevent the modulating valve from moving beyond
the cracked position until the downstream main is proven to be
free of condensate and starting to warm up.
Condensate-Return
Problems
Condensate-return
problems often are the result of problems concerning the application
of modulating control valves to steam loads. Most steam loads are
equipped with a control valve because their capacity requirements
vary. When a steam-control valve throttles, it reduces the pressure
at which steam condenses. In a saturated system, reducing pressure
reduces temperature and, thus, heat transfer. In steam systems,
some of the temperatures required to serve HVAC loads result in
subatmospheric pressures in the heat-transfer elements, especially
at part-load conditions. If a heat-transfer element is connected
to a vented return system,9 no pressure difference is
available to force condensed steam out of the heat-transfer element
until enough condensate accumulates to create the necessary gravity
head.10 As a result, numerous problems can occur, including:
- The loss
of heat-transfer capacity because the backed-up condensate required
to produce the necessary gravity head reduces the heat-transfer
surface available to the steam. This can lead to extreme temperature
oscillation leaving the load, as the flooding of the heat exchanger
fights with the heat-transfer-surface area and temperature-difference
requirement necessary to serve the load.
- Waterhammer,
difficulty predicting system performance, and difficulty sizing
valves--all because of the cyclical nature of the process described
above.
- The condensate
backed up into the tubes freezing quickly when subjected to air
at subfreezing conditions--if the heat exchanger is a steam coil
in a preheat position.11 Condensate-return problems
also can be associated with improper pitching and trapping of
steam-supply piping. Even when insulated, steam-supply piping
will lose heat to its surroundings. This loss causes minor condensation
whenever the piping system is active. The condensation that occurs
when the piping is started can be several orders of magnitude
greater than the condensation associated with parasitic losses
during operation. If this condensation is not removed, it will
impede the flow of steam through the system and eventually cause
waterhammer. This can be avoided by pitching the piping (ideally,
in the direction of flow) so that the condensate can drain toward
a load or to a trap installed on a drip leg at a low point in
the system.12
If these issues
are not addressed during the design and fabrication of the piping
system, they will show up as commissioning and operational problems.
In some cases, they can lead to costly--and even catastrophic--equipment
failures. By reviewing the design and installation of the steam-
and condensate-system piping and the associated load connections
during the design phase of a project, a commissioning agent can
mitigate and avoid condensate-return problems. It is important to
keep in mind that:
- Unless
a vacuum condensate-return system is scrupulously installed and
maintained, it is best to assume that it will operate as a vented
gravity return system because of leaks in the piping circuit and/or
trap failures.
- All vented
gravity return piping should depend solely on gravity to move
condensate from the load to the condensate receiver and pump.
Even a relatively modest elevation change cannot be tolerated
because the vented return system provides no motivation for the
condensate to flow uphill against the force of gravity (Photo
C).
PHOTO C. This 10-in. change in the elevation of return piping
trapped a large slug of water upstream, flooding the load. The untrapped
elevation change in the parallel steam line (behind the return line)
prevented condensation from draining properly, resulting in waterhammer.
- Applying
vacuum breakers to all loads served by modulating valves can help
ensure good gravity drainage. Basically, these devices are check
valves that allow air to enter a heat exchanger when the pressure
inside becomes subatmospheric. It is important to understand,
however, that the return system still has to be designed to drain
condensate away from the steam reheat coil (Photo D). Also, vacuum
breakers are not without faults. Allowing air to enter a steam
system can create heat-transfer problems of its own, as the heat
exchanger is filled with a mix of air and steam.6 This
air can cause corrosion in the return system. These issues, however,
usually can be dealt with via the proper location and piping of
the vacuum breaker6 and a good water-treatment program. In short,
the vacuum breaker generally solves more problems than it creates.
PHOTO D. This modest (less than 2 ft) change in the elevation of
return piping from a steam reheat coil creates a condition that
sees the coil flood until the reduced heat-transfer surface causes
the steam valve to open and introduce steam at a pressure high enough
to blow the condensate up into the elevated return main. This sudden
change in available heat-transfer surface causes an excessive supply
temperature, which results in cycling and instability. This coil
was equipped with a vacuum breaker. However, that only guarantees
that the coil always will be at or above atmospheric pressure and
that it will drain somewhat predictably to a gravity return system.
It cannot cause the condensate to flow uphill.
Some additional
advice:
- On the outlet
of the load, include a piping drop that is long enough to ensure
that gravity drainage from the load will create a fluid head above
the steam trap under all load conditions. Size the trap conservatively
based on that head.
- Always
pitch heat-transfer elements toward the drain connection to ensure
gravity drainage.
- Do not
modulate a control valve for a preheat coil when the entering
temperature is below freezing. Instead, keep the valve wide open,
and use some other means, such as face and bypass dampers, to
achieve temperature control.13
- Make sure
the supply system is properly pitched and provided with drip legs
and traps wherever there is a rise in the piping. Various trap
designs are available, with some better than others for a given
application. Generally, a trap that continuously drains condensate,
such as a float-and-thermostatic trap, best serves modulating
loads. Applications that must lift condensate with the available
inlet pressure often are best served with two position traps,
such as bucket traps. Traps used on vacuum return systems must
be designed specifically for that service.
Conclusion
Considering
the integrated operating requirements of systems in which steam
valves are installed is essential if full functionality is to be
realized. A steam valve will fail to perform as intended if sizing
and installation issues are not fully considered, even if the material
and application specifications are correct. By paying attention
to the details of valve installation and taking time to understand
the physical principles behind steam-system design, commissioning
and operating personnel can mitigate and readily correct a host
of problems.
Footnotes
1) This pressure
drop often can be based on the difference between the steam entering
pressure and the condensing pressure in the load served. Typically,
the entering pressure will be set based on the pressure settings
of the boiler-firing controller minus any losses caused by flow
between the boiler location and the valve location.
2) It is important
to use absolute pressure, not gauge pressure, when sizing steam
valves. This can be accomplished by adding 14.7 psi (atmospheric
pressure) to the gauge pressures.
3) The valve-sizing
equations presented in this article can be found in Chapter 42 of
the ASHRAE 2000 Systems and Equipment Handbook. They also may be
found in other sources, including control-system textbooks and literature
from manufacturers. In reviewing these other sources, you may discover
slight differences in the constants and the point defined as the
transition from critical to non-critical flow.
) For example,
an equal-percentage valve often is a good choice for application
with a heat exchanger because the non-linearity of one will cancel
out the non-linearity of the other, resulting in a linear or near-linear
relationship between valve position and energy transfer. See Page
42.8 of the ASHRAE 2000 Systems and Equipment Handbook for a graphical
depiction of this. Additional information can be found in the article
"Control Valve Selections for Hydronic Systems" by Mark
C. Hegberg in the November 2000 issue of ASHRAE Journal.
5) To learn
more about this approach, see Moore Products Co. Application Data
Sheet AD352-106, which can be downloaded at www.sea.siemens.com/
instrbu/docs/pdf/Ad352-106.PDF.
6) This approach
needs to be used with caution with electrically driven actuators
because the lubrication of the gear train can be sensitive to position.
7) The loads
can be in excess of the drip-trap capacity if the line is warmed
up too rapidly, insulation is missing from a portion of the circuit,
or traps serving the circuit failed during shutdown.
8) This can
damage the piping circuit and lead to injury or loss of life. To
learn more, read "Condensation-Induced Waterhammer" and
"What Caused the Steam System Accident That Killed Jack Smith?",
both by Wayne Kirsner, PE, in the January 1999 and July 1995 issues
of Heating/Piping/Air Conditioning, respectively.
9) Although
this is not the only possible arrangement, it, by far, is the most
common--either by design or because of the failure of a component
in a vacuum return system.
10) For more
on this phenomenon, see "Fundamentals of Steam Heating Systems"
by William J. Coad, PE, in the November 1995 issue of Heating/Piping/
Air Conditioning.
11) Not all
heating coils can function as preheat coils. Even a steam coil will
freeze if it is not selected, piped, and controlled in a manner
that allows it to safely handle subfreezing air.
12) For a discussion
of drip legs and other piping issues, see "Troubleshooting
Steam-System Problems" by Walter T. Deacon in the November
2001 issue of HPAC Engineering.
13) When conditions
are above freezing, valve modulation can be sequenced with face
and bypass dampers to achieve energy savings. Do not forget to fully
close the valve when preheat no longer is needed because the active
elements in the preheat coil represent a parasitic load on the steam
and air-handling system, even with no airflow.
David A.
Sellers, PE, is a senior engineer specializing in commissioning
and energy efficiency. Over the course of his career, he has worked
in the design, mechanical- and controls-contracting, and facilities-engineering
fields in the commercial-, institutional-, and industrial-buildings
industries.
|